[Exigences d'évaluation du CCMC] CAN/ULC-S702-14, type 2

De : Conseil national de recherches Canada

Le présent document résume les exigences minimales imposées par le Centre canadien de matériaux de construction (CCMC) pour toutes les évaluations fondées sur les critères énoncés dans le document ci-après. Pour certaines évaluations, et au besoin, des exigences supplémentaires pourraient être imposées par le CCMC, ces dernières étant détaillées dans l'évaluation en question.

Document énonçant les critères d'évaluation

Portée

These evaluations apply to mineral fibre thermal insulation in the form of faced and unfaced batts, rolls, and boards.

The standard describes five types of mineral fibre insulation. These CCMC evaluations refer only to preformed insulation Type 2. They are defined as preformed insulation (in the form of batts, rolls or boards) with a permeable membrane on one or both faces.

Exigences matérielles

Le titulaire de l'évaluation doit démontrer que le produit satisfait aux exigences suivantes (au besoin, des exigences supplémentaires pourraient être imposées par le CCMC, et ces dernières sont détaillées dans l'évaluation en question) :

Tableau 1. Requirements for preformed thermal insulation - Type 2
Property Requirement
Length –1%, +3% for batts and rolls
–3 mm, +10 mm for boards
Width –0%, +3% for batts and rolls
± 3 mm for boards
Thickness Mean thickness ≥ the design thickness and none of the individual specimen thicknesses < 90% of the design thickness for batts and rolls
–1 mm, +3 mm for boards
Thermal resistance Mean thermal resistance ≥ the design thermal resistance (as stated on the product)
Thermal resistivity ≥ 18.5 (m·K)/W
Surface burning characteristics For Types 2 and 3 the test values shall be reported without reference to the acceptance criteria.
Breaking load of exterior frame wall sheathing Not applicable to batts or rolls. Applicable only to Type 2 boards for exterior frame wall sheathing.
≥ 2.7 kg for boards
Compressive resistance of draining insulation Not applicable to batts or rolls. Applicable to draining insulation only. Compressive resistance for 38 mm or thicker draining insulation shall be at least 7 kPa at 10 % deformation and for thinner than 38 mm it shall be at least 10 kPa at 25 % deformation.
≥ 7 kPa or ≥ 10 kPa
Water vapour permeance ≥ 300 ng/(Pa·s·m2) for batts and rolls
Applicable to adhered membrane/ insulation or to non-adhered membranes for boards
Corrosiveness Not applicable for batts and rolls
Corrosion ≤ control for boards
Fungi resistance Not applicable for batts and rolls
Growth ≤ comparative item for boards


© Laboratoires des assureurs du Canada Inc. Reproduit sous autorisation. Le présent document ne représente pas la position complète et officielle de Normes ULC sur le sujet mentionné, laquelle est représentée uniquement par la norme ULC dans son intégralité.

Exigences relatives à l'installation

Le CCMC exige que les titulaires d'évaluation fournissent des instructions d'installation de produits qui :

Exigences relatives à la fabrication

Le CCMC exige que les titulaires d'évaluation puissent, à tout le moins, démontrer que le processus de production associé :

Exigences relatives à l'étiquetage

Le CCMC exige des titulaires d'évaluation qu'ils s'assurent que les étiquettes des produits :

The standard requires that packaging for the insulation be labelled or marked with the following information:

  • brand name and the name of the manufacturer or supplier;
  • identification of the manufacturing facility location;
  • type of insulation and its intended use;
  • net content of package in m2;
  • number of pieces per package;
  • design linear dimensions of the pieces in the package in mm;
  • design thickness in mm;
  • thermal resistance in (m2·K)/W to one decimal place
  • date of manufacture or shift code;
  • statement that the product complies with the standard; and
  • for preformed insulation without a membrane (Type 1 material), except for draining insulation, a cautionary statement:
    “CAUTION: Building, electrical, fire and other applicable codes shall be complied with. All heat-emitting devices, such as fuelburning appliances, chimneys, pipes, ducts and vents to these appliances shall maintain a minimum clearance of 50 mm between these devices and the insulation. Recessed light fixtures, unless designed for the purpose, shall not be installed in insulated ceilings."
Where applicable, the product must carry additional information as stated below:
  • If the product is intended for application at thicknesses other than the design thickness, the thermal resistance and application for each intended secondary application must be shown in similar print at a character height of at least half that of the design characters (with a minimum of 15 mm). The associated thickness of the secondary application must also be shown. This secondary application, thermal resistance and thickness information must be located on the same sides, excluding the ends, of the package as the design thermal resistance, application and thickness designations.
  • Any necessary user safety information, unless a separate information sheet is provided.

Depending upon the jurisdiction, additional marking may be required by applicable acts and regulations.

Renseignements sur la classification

Les produits visés par le présent document sont généralement classés dans :

Répertoire normatif (MasterFormatᴹᴰ)

  • 07 20 00 Thermal Protection
  • 07 21 13 Isolation des panneaux
  • 07 21 13.16 Fibrous Board Insulation
  • 07 21 13.19 Mineral Board Insulation
  • 07 21 16 Blanket Insulation
  • 09 81 00 Acoustic Insulation
  • 09 81 13 Acoustic Board Insulation
  • 09 81 16 Acoustic Blanket Insulation

Évaluations du CCMC publiées

Les produits suivants ont été évalués par le CCMC en fonction de ces exigences :

Numéro du CCMC :Fabricant :Noms des produits :
14060-LThermafiber Inc./Owens Corning FireSpan® 90, VersaBoard® 35, RainBarrier® 45, FireSpan® 40, RainBarrier® HD, VersaBoard® 40, VersaBoard® 80, VersaBoard® 60, RainBarrier® CI High Compressive (80), RainBarrier® CI Plus (110), RainBarrier® CI Max, RainBarrier® HD Dark™, RainBarrier® 45 Dark™, Thermafiber® Safing

Renvoi aux codes

Code national du bâtiment du Canada 2015

Renvoi aux codes Disposition
9.25.2.2. 1)Sous réserve du paragraphe 9.25.2.2.(2), ...
A-5.9.1.1. 1)Choix des matériaux et des composantset conformité aux normes incorporées par renvoi
A-9.36.2.4. 1)Calcul de la résistance thermiqueeffective des ensembles de l’enveloppe du bâtiment
Tableau 5.9.1.1.Normes applicables aux éléments de séparation des milieuxdifférents et aux ensembles de construction exposésau milieu extérieur
Tableau 9.23.17.2.AÉpaisseur et caractéristiques des revêtements muraux intermédiaires