[CCMC 14722-R] CCMC Canadian code compliance evaluation
From: National Research Council Canada

CCMC number: | 14722-R |
Status: | Active |
Issue date: | 2023-03-24 |
Modified date: | 2023-08-03 |
Evaluation holder: | DMX Membranes Limited
165 Orenda Road |
Product name: | DMX AG-2™ |
Compliance: | OBC 2017 |
Criteria: |
|
In most jurisdictions this document is sufficient evidence for approval by Canadian authorities.
Learn more about CCMC recognition Look for the trusted CCMC mark on products to verify compliance.Compliance opinion
It is the opinion of the Canadian Construction Materials Centre that the evaluated product, when used as foundation wall drainage material in accordance with the conditions and limitations stated in this evaluation, complies with the following code:
Ontario Building Code 2017
ID | Code provision | Solution type |
---|---|---|
09-14-02-01-02-b-00 | 9.14.2.1.(2)(b) Foundation Wall Drainage | Acceptable |
The above opinion(s) is/are based on the evaluation by the CCMC of technical evidence provided by the evaluation holder, and is bound by the stated conditions and limitations. For the benefit of the user, a summary of the technical information that forms the basis of this evaluation has been included.
Product information
Product name
DMX AG-2™
Product description
The product is a high-density, low-heat formed, polyethylene sheet roll. The material has a dimpled surface on one side that provides an air gap between the concrete wall and the adjacent soil. The sheet thickness is approximately 0.7 mm. The product is available in rolled sheet form that is 1.22 to 2.44 m (4 to 8 ft.) wide and 20 m (65.5 ft.) long. When two sheets are joined side by side, they must be overlapped by 200 mm to 300 mm with the dimples meshing.
To ensure correct application, a range of accessories, such as fasteners, anchors and moulding strips, are included with the product. Photos of the product can be seen in Figure 1 and Figure 2 below.
Figure 1. DMX AG-2™ product rolls
Figure 2. DMX AG-2™ anchor
Manufacturing plant
This evaluation is valid only for products produced at the following plant:
Product name | Manufacturing plant |
---|---|
Brampton, ON, CA | |
DMX AG-2™ | Product evaluated by the CCMC |
Product evaluated by the CCMC Indicates that the product from this manufacturing facility has been evaluated by the CCMC
Conditions and limitations
The CCMC’s compliance opinion is bound by this product being used in accordance with the conditions and limitations set out below.
- Based on the evidence provided, the product has been classified as Type 2, Class B (cups facing soil).
- The Class B product is a dimpled membrane designed to act as a protective layer or a capillary-breaking layer against the foundation wall to protect the wall against transient or intermittent water that may come in contact with its surface.
- The Type 2 product has been evaluated for use in vertical applications in depths up to 3.7 m below grade. Applications greater than 3.7 m are considered to be outside the scope of this evaluation.
- The product must be installed in accordance with the manufacturer’s instructions. In the event of conflict between the manufacturer’s instructions and local building codes, local building codes shall govern.
- The product was evaluated for use against cast-in-place and concrete block foundations, and must cover the foundation wall from the top of the footing to the final grade.
- Unit masonry walls and concrete walls shall have all holes and recesses sealed with mortar. The product must be installed on surfaces that are clean and dry, and free of ice, snow, frost, dust, dirt, oil, grease, cracks, projections and depressions, loose particles, and debris.
- The product is only one portion of the total foundation drainage system, which consists of a combination of design and construction processes that use different products. In particular, the product must be bent at the footing to guide water past the cold joint to a drainage pipe located outside of the footing at the bottom of the wall. This pipe will drain the water collected by the product toward an outflow (i.e., sewer). The product relies on a foundation wall drainage system that conforms to either Subsection 9.14.3., Drainage Tile and Pipe, or Subsection 9.14.4., Granular Drainage Layer, of Division B of the OBC 2017.
- The placement and grading of backfill must conform to the requirements of Subsection 9.12.3., Backfill, of Division B of the OBC 2017. It is recommended that an impervious “topping off” layer of clay or silt material be placed on top of the backfill with a positive slope leading surface water away from the building.
- The product must be protected from exposure to ultraviolet (UV) light (sunlight) within a maximum of 30 days of its installation.
- Long-term performance of a drainage system will depend on local conditions, such as the soil type, hydrogeology of the site, mineralogy and presence of microorganisms in the soil (i.e., iron ochre). Compliance with this evaluation does not free the project from requiring proper engineering design of the drainage system.
- The performance of the fixture used to anchor the product in the wall was evaluated. It is the responsibility of the manufacturer to define the pattern and spacing of anchors, considering the anchor strength as well as site-specific issues, such as the type of soil, how it will interact with the product and the backfilling method used.
- The top of the membrane and all vertical joints and terminations must be mechanically fastened with trims, molding strips, termination bars or other accessories to prevent soil particles from entering behind the membrane. Overlaps or joints that are occasionally exposed to a head of water must be sealed to avoid water entry and associated dragging of soil particles between the membrane and the foundation wall. Accessories used to anchor the product are part of the evaluation.
- The products’ label and/or packaging must be clearly identified with the following:
- the manufacturer’s name or logo; and
- the phrase “CCMC 14722-R”.
Technical information
This evaluation is based on demonstrated conformance with the following criteria:
Criteria number | Criteria name |
---|---|
CCMC-TG-334623.01-15 | CCMC Technical Guide for Foundation Wall Drainage Systems – Dimpled Membranes |
Property | Unit | Requirement | Result |
---|---|---|---|
Compressive strength (initial) | kPa | ≥ 150 | 199.4 |
Dynamic impact resistance (mean failure energy) | J | ≥ 2.45 | 11.1 |
Creep resistance (residual thickness at 25 years/10°C) | % | ≥ 40% | 87.8 |
Cold bending at –30°C | N/A | No visible crack | No visible crack |
Tensile strength – at yield | kN/m | ≥ 8 | MD 10Table 1. footnote (1) XD 9.1 |
Tensile strength – elongation at break in cross direction | % | ≥ 25 | MD 42.5Table 1. footnote (1) XD 32.8 |
Tensile strength – anisotropy ratio | – | ≥ 0.5 | 1.11 |
Heat aging for 2 weeks – OIT after 2 weeks | min | ≥ 5 | 17.8Table 1. footnote (2) |
Heat aging for 2 weeks – dimensional change | % | ≤ 1 |
–0.5 (length), –0.7 (width) |
Heat aging for 2 weeks – weight change | % | ≤ 0.1 | –0.2Table 1. footnote (3) |
Heat aging for 2 weeks – residual compression strength | % | ≥ 80% of initial | 128.7 |
Heat aging for 2 weeks – creep resistance after heat aging (residual thickness at 25 years/10°C) | % | ≥ 40 | 89.0 |
Resistance to alkaline environment – appearance | N/A | No visible crack | No visible crack |
Resistance to alkaline environment – residual compression strength | % | ≥ 80% of initial | 126.2 |
Resistance to alkaline environment – appearance (cold bending at –30°C) | N/A | No cracks at room temperature | No visible crack |
Geometrical properties | |||
Orientation of dimples | – | Report value | Perpendicular |
Number of dimples per unit area | Dimples/m2 | Report value | 1 294 |
Overall thickness | mm | Report value | 7.74 |
Sheet thickness | mm | Report value | 0.68 |
Hollow core thickness | mm | ≥ 5 | 7.06 |
Anchorage performance | kN/anchor | Report value | 0.393 |
Administrative information
Use of Canadian Construction Materials Centre (CCMC) assessments
This assessment must be read in the context of the entire CCMC Registry of Product Assessments, any applicable building code or by-law requirements, and/or any other regulatory requirements (for example, the Canada Consumer Product Safety Act, the Canadian Environmental Protection Act, etc.).
It is the responsibility of the user to confirm that the assessment they are using is current and has not been withdrawn or superseded by a later version on the CCMC Registry of Product Assessments.
Disclaimer
The National Research Council of Canada (NRC) has evaluated only the characteristics of the specific product described herein. The information and opinions in this evaluation are directed to those who have the appropriate degree of experience to use and apply its contents (such as authorities having jurisdiction, design professionals and specifiers). This evaluation is valid when the product is used as part of permitted construction, respecting all conditions and limitations stated in the evaluation, and in accordance with applicable building codes and by-laws.
This evaluation is provided without representation, warranty or guarantee of any kind, expressed or implied, and the NRC provides no endorsement for any evaluated product. The NRC accepts no responsibility whatsoever arising in any way from any and all use of or reliance on the information contained herein or the use of any evaluated product. The NRC is not undertaking to render professional or other services on behalf of any person or entity nor to perform any duty owed by any person or entity to another person or entity.
Language
Une version française de ce document est disponible.
In the case of any discrepancy between the English and French version of this document, the English version shall prevail.
Copyright
© His Majesty the King in Right of Canada, as represented by the National Research Council of Canada, 2023
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, without the prior written permission of the CCMC.