[CCMC 14067-R] CCMC Canadian code compliance evaluation
CCMC number: | 14067-R |
Status: | Active |
Issue date: | 2017-08-18 |
Modified date: | 2023-11-15 |
Evaluation holder: | Elastochem Specialty Chemicals Inc.
37 Easton Road |
Product name: | Wrapsulate® Foam Jacket |
Compliance: | NBC 2015, NBC 2020, OBC |
Criteria: |
|
In most jurisdictions this document is sufficient evidence for approval by Canadian authorities.
Learn more about CCMC recognition Look for the trusted CCMC mark on products to verify compliance.Compliance opinion
It is the opinion of the Canadian Construction Materials Centre that the evaluated product, when used as a thermal insulation in accordance with the conditions and limitations stated in this evaluation, complies with the following codes:
National Building Code of Canada 2015
ID | Code provision | Solution type |
---|---|---|
9.25.2.2. Insulation Materials | Alternative |
National Building Code of Canada 2020
ID | Code provision | Solution type |
---|---|---|
9250202000000 | 9.25.2.2. Insulation Materials | Alternative |
Ontario Building Code
Ruling No. 14-07-303 (14067-R) authorizing the use of this product in Ontario, subject to the terms and conditions contained in the Ruling, was made by the Minister of Municipal Affairs and Housing on 2014-09-23 pursuant to s.29 of the Building Code Act, 1992 (see Ruling for terms and conditions). This Ruling is subject to periodic revisions and updates.
The above opinion(s) is/are based on the evaluation by the CCMC of technical evidence provided by the evaluation holder, and is bound by the stated conditions and limitations. For the benefit of the user, a summary of the technical information that forms the basis of this evaluation has been included.
Product information
Product name
Wrapsulate® Foam Jacket
Product description
The product is a Type 2, spray-in-place, low density, semi-flexible plastic foam that has an open cell structure. The product consists of “Wrapsulate® Foam Jacket” Part A isocyanate and “Wrapsulate® Foam Jacket” Part B resin, which are mixed on-site by a qualified installer using positive displacement equipment in a 1:1 fixed ratio.
The final cured product is yellow and has a density of 17 kg/m3 (1.06 lb/ft3 ). At a thickness of 25.4 mm (1 in.), the thermal resistance is RSI 0.75 (m2 ·°C/W) R-4.3 (ft2 ∙°F∙hr/BTU∙in.).
Site-manufactured product
This is a site-manufactured product; it must be finished on site only by certified installers through the spray-application of raw materials bearing a CCMC number that are produced only at the manufacturing plant(s) below. See installation of spray-applied polyurethane insulation for more information on the requirements for installation and site quality assurance.
Manufacturing plant
This evaluation is valid only for products produced at the following plant:
Product name | Manufacturing plant |
---|---|
Brantford, ON, CA | |
Wrapsulate® Foam Jacket | Product evaluated by the CCMC |
Product evaluated by the CCMC Indicates that the product from this manufacturing facility has been evaluated by the CCMC
Conditions and limitations
The CCMC’s compliance opinion is bound by this product being used in accordance with the conditions and limitations set out below.
- This is a site-manufactured product whereby the installation of spray-applied polyurethate foam must be performed following a site quality assurance program by certified installers trained by the evaluation holder (or their representative) and licensed by the designated SQAP provider.
- The product can be installed in new or retrofit construction. In either case, the product must be installed in open cavities in the following locations in a wood-frame construction that meets the requirements of the NBC 2015 (see Figure 1):
- exterior walls including perimeter joists;
- cathedral ceilings with a vented air space as required by the NBC 2015;
- floors separating living spaces from a garage;
- cantilever overhang floors; and
- interior below-grade foundation walls.
- The building envelope where the product is installed must conform to the requirements of the NBC 2015 for vapour barriers, air barriers, and dampproofing (interior below-grade walls).
- For retrofit applications whereby there may be occupants in the unaltered part of the building, the qualified installer must ensure that the spraying area is isolated and negatively pressurized by using an exfiltration rate of 0.3 air changes per hour for at least twenty-five (25) hours. An independent toxicological assessment determined that this ventilation rate must also be in effect for twenty-five (25) hours before occupancy is permitted in the newly insulated suite.
- The sprayed material should completely cover the surfaces between the studs, joists and other framing members. The surfaces to be covered should be clean, dry, and not covered in frost, oil, grease, dust or another unsuitable material. As required in Article 9.25.2.3., Installation of Thermal Insulation, of Division B of the NBC 2015, the insulation must be installed so that there is a reasonably uniform insulating value over the entire face of the insulated area.
- The interior side of the applied semi-flexible polyurethane insulation must be covered with an approved thermal barrier as per Article 9.10.17.10., Protection of Foamed Plastics, of Division B of the NBC 2015.
- The insulation must be kept away from heat-emitting devices, such as recessed light fixtures and chimneys, at the minimum distance required by building regulations and safety codes.
- The maximum in-service temperature of the insulation must not exceed 70°C.
- The product must not be installed after its expiry date of six (6) months from the date of manufacture.
- The isocyanate and resin components must have their respective containers (i.e., drums) identified with the phrase “CCMC 14067-R.”
- The installation procedure must follow the manufacturer’s installers manual. A copy of the manual must be available at the job site at all times during the installation for review by the building officials.
Technical information
This evaluation is based on demonstrated conformance with the following criteria:
Criteria number | Criteria name |
---|---|
CCMC-TG-072119.03-15 | CCMC Technical Guide for Spray-in-Place, Open-Cell Polyurethane Foam (OPF) Thermal Insulation |
CCMC-TG-072119.03-20 | CCMC Technical Guide for Spray-in-Place, Open-Cell Polyurethane Foam (OPF) Thermal Insulation |
Performance requirements
Property |
Unit |
Requirement |
Result |
---|---|---|---|
Density |
kg/m3 |
≥ 6.8 |
17 |
Thermal resistance for 25-mm thickness |
m2°C/W |
Report value |
0.75 |
Water vapour transmission for 25-mm thickness |
ng/(Pa·s·m2) |
≥ 800 (Type 2) |
1 175 (average of 3 tests) |
Water absorption |
% |
< 5 (Type 2) |
1.39 (average of 4 tests) |
Dimensional changes when exposed to 80°C and ambient RH |
% volumetric |
Min. –15 Max. +10 |
–9.0 (average of 3 tests) |
Dimensional changes when exposed to 70°C and 97 ± 3% RH |
% volumetric |
Min. –15 Max. +14 |
–2.3 (average of 3 tests) |
Dimensional changes when exposed to -29°C and ambient RH |
% volumetric |
Min. –1 - |
0.3 (average of 3 tests) |
Emissions – time to occupancy |
|
Pass |
Other technical evidence
Additional performance data requested by the report holder
Data in this section does not form part of CCMC’s opinion in Section 1.
Fire protection requirements
Property |
Requirement |
Result |
---|---|---|
Flame-spread ratingTable footnote (3)(CAN/ULC-S102 and CAN/ULC-S127) |
Report value |
174 |
Smoke development |
Report value |
495 |
In addition to the material qualification above spray-applied polyurethane foams must be installed in accordance with their respective installation standard and under a Site Quality Assurance Program (SQAP). This evaluation holder has engaged the designated SQAP provider below to operate it's SQAP program for the installation of this product by certified installers, and to provide third-party site auditing, as required. As with any evaluation, the evaluation holder is responsible for the quality of the finished product (installed foam), and therefore is required to ensure resolution of non-conforming installations. The installation procedure must follow the manufacturer’s instruction manual. A copy of the manual must be available at the job site at all times during the installation for review by the building official. The evaluation holder requires that only specific, certified installers be authorized to install its proprietary spray-polyurethane insulation in buildings. All installers must be certified for the installation of this product by the designated SQAP provider, having a valid photo-identification license at the time of installation, and be able to present the license on request. As part of its SQAP, the evaluation holder also stipulates that periodic site-audit inspections be conducted by the designated SQAP provider. Upon completion of the site audit, the designated SQAP provider will report the product’s conformity results and any corrective action required, if necessary, to the evaluation holder. Building officials can contact the SQAP provider to request a site-audits at a specific building site. The following organization has been designated by the evaluation holder as their SQAP provider, and is recognized by the CCMC as an ISO/IEC 17024 accredited personnel certification body, and ISO/IEC 17020 accredited inspection body. Urethane Foam Consultants (UFC)Site quality assurance program (SQAP)
Installation of spray-applied polyurethane insulation
Certified installers
Third-party site auditing
Designated SQAP provider
160 Main Street South, Suite 547
Brampton, Ontario, L6W 4C1
Telephone: 905-702-2555
Fax: 905-456-9439
Website: foamexperts.ca
Administrative information
Use of Canadian Construction Materials Centre (CCMC) assessments
This assessment must be read in the context of the entire CCMC Registry of Product Assessments, any applicable building code or by-law requirements, and/or any other regulatory requirements (for example, the Canada Consumer Product Safety Act, the Canadian Environmental Protection Act, etc.).
It is the responsibility of the user to confirm that the assessment they are using is current and has not been withdrawn or superseded by a later version on the CCMC Registry of Product Assessments.
Disclaimer
The National Research Council of Canada (NRC) has evaluated only the characteristics of the specific product described herein. The information and opinions in this evaluation are directed to those who have the appropriate degree of experience to use and apply its contents (such as authorities having jurisdiction, design professionals and specifiers). This evaluation is valid when the product is used as part of permitted construction, respecting all conditions and limitations stated in the evaluation, and in accordance with applicable building codes and by-laws.
This evaluation is provided without representation, warranty or guarantee of any kind, expressed or implied, and the NRC provides no endorsement for any evaluated product. The NRC accepts no responsibility whatsoever arising in any way from any and all use of or reliance on the information contained herein or the use of any evaluated product. The NRC is not undertaking to render professional or other services on behalf of any person or entity nor to perform any duty owed by any person or entity to another person or entity.
Language
Une version française de ce document est disponible.
In the case of any discrepancy between the English and French version of this document, the English version shall prevail.
Copyright
© His Majesty the King in Right of Canada, as represented by the National Research Council of Canada, 2024
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, without the prior written permission of the CCMC.
Page details
From: National Research Council Canada
- Date modified: