[CCMC 14280-R] CCMC Canadian code compliance evaluation

From: National Research Council Canada

In most jurisdictions this document is sufficient evidence for approval by Canadian authorities.

Learn more about CCMC recognition Look for the trusted CCMC mark on products to verify compliance.

Compliance opinion

It is the opinion of the Canadian Construction Materials Centre that the evaluated products, when used as a soil gas (radon) barrier in accordance with the conditions and limitations stated in this evaluation, comply with the following code:

National Building Code of Canada 2015

ID Code provision Solution type
09-13-04-02-00-0-009.13.4.2.(1) All wall, roof and floor assemblies sepa ...Acceptable
09-25-03-06-00-0-009.25.3.6.(1) Materials used to provide a barrier to t ...Alternative

The above opinion(s) is/are based on the evaluation by the CCMC of technical evidence provided by the evaluation holder, and is bound by the stated conditions and limitations. For the benefit of the user, a summary of the technical information that forms the basis of this evaluation has been included.

Product information

Product names

  • Airmetic® SOYA HFO - Radon Protection System
  • Heatlok® SOYA HFO - Radon Protection System
  • Polarfoam SOYA HFO - Radon Protection System

Product description

The product is an under-slab barrier designed to restrict naturally occurring radon gas from migrating through the ground and concrete slab. It is a closed-cell, spray-applied rigid polyurethane foam of medium density, evaluated under CCMC 14078-L, and consists of two components that must be labelled as follows:
  • Isocyanate (Component A): A100 Isocyanate; and
  • Resin (Component B): Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polarfoam SOYA HFO resin.

The two components are mixed on site by Huntsman Building Solutions (Canada) Inc.-qualified installers (see the Qualified installers section below) with fixed-ratio positive displacement equipment. The colour of the installed final cured Heatlok® SOYA HFO and Airmetic® SOYA HFO products are green. The colour of the installed final cured Polarfoam SOYA HFO product is peach. 

Qualified installers and site quality assurance program (SQAP)

Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polarfoam SOYA HFO for radon control is a site-manufactured product, whereby Huntsman Building Solutions (Canada) Inc. requires that only specific qualified installers be authorized to install their proprietary spray polyurethane insulation in buildings. In accordance with the Huntsman Building Solutions (Canada) Inc. site quality assurance program (SQAP), the certification organization Caliber Quality Solutions Inc. (Caliber) has been commissioned to license the specified installers and issue them the requisite Caliber identification card. Note that the training and installer certification to install Heatlok® SOYA HFO, Airmetic SOYA HFO, Polarfoam SOYA HFO for radon control is in addition to the base Caliber/Huntsman Building Solutions (Canada) Inc. training for the spraying of polyurethane foam as a thermal insulation only in accordance with CAN/ULC-S705.2-05(R2016), “Thermal Insulation – Spray Applied Rigid Polyurethane Foam, Medium Density – Application”). As part of their SQAP, Huntsman Building Solutions (Canada) Inc. also stipulates that site-audit inspections be conducted by site inspectors licensed by Caliber. Upon completion of the site audit, Caliber will report the product’s conformity results and any corrective action required, if necessary, to Huntsman Building Solutions (Canada) Inc. Building officials who would like site-audit inspections to be conducted on specific building sites can contact Caliber (see details in CCMC 14078-L).

All specified installers must present a Caliber identification card to the building official that indicates the installer is certified to install the spray foam for both intended functions; that is, as a thermal insulation (CAN/ULC-S705.2-05(R2016)) and as an air/radon barrier.

Thickness – spray foam and gravel drainage layer

Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polarfoam SOYA HFO for radon control requires a minimum of 38-mm spray polyurethane to be installed. The spray polyurethane may be sprayed directly over the NBC-specified 100-mm gravel bed or onto a geotextile. When applied directly over the gravel bed, the foam resin may penetrate up to 24 mm into the cavities between the surface gravel. For direct gravel applications, the gravel bed shall be increased to 124 mm to ensure a minimum 100-mm gravel bed as the gas-permeable layer to evacuate the radon gas.

Radon resistance

It should be noted that Sentence 9.13.4.2.(1) of Division B of the NBC 2015 requires an effective air barrier system be installed as a barrier to soil gas. Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polarfoam SOYA HFO has qualified as an air barrier system required by the NBC 2015 for soil gas, as outlined in Table 2, air barrier system performance and, in Table 3, effective barrier performance to, specifically, radioactive radon. Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polarfoam SOYA HFO, when installed at 38 mm, shows better resistance to radon than 6-mil polyethylene (that is, the NBC 2015 benchmark acceptable solution).

Manufacturing plant

This evaluation is valid only for products produced at the following plant:

Product namesManufacturing plant
Boisbriand, QC, CA
Airmetic® SOYA HFO - Radon Protection SystemProduct evaluated by the CCMC
Heatlok® SOYA HFO - Radon Protection SystemProduct evaluated by the CCMC
Polarfoam SOYA HFO - Radon Protection SystemProduct evaluated by the CCMC

Product evaluated by the CCMC Indicates that the product from this manufacturing facility has been evaluated by the CCMC

  Conditions and limitations

The CCMC’s compliance opinion is bound by this product being used in accordance with the conditions and limitations set out below.

  • The system must be applied on site by qualified installers who are Huntsman Building Solutions (Canada) Inc.-trained and Caliber-certified and who possess a Caliber identification card.(1) The SQAP and installation manual shall be available on site for review by the local authority having jurisdiction (AHJ).
  • The thickness of the specified medium-density spray polyurethane foam shall be a minimum of 38 mm when installed over geotextile. When sprayed directly onto the gravel, the NBC-specified 100-mm gravel bed shall be increased to 124 mm for 3/4 in. gravel and to 118 mm for 1/2 in. and 1/4 in. gravel. Per Sentence 9.16.2.1.(1), Required Installation of Granular Material, of Division B of the NBC 2015, the specified gravel shall consist of coarse, clean granular material containing not more than 10% of material that will pass a 4 mm sieve.
  • A minimum of 24 h shall pass before the installation of the 100-mm concrete floor slab.
  • As with the 6-mil polyethylene sheet, care shall be taken to not damage the spray polyurethane surface during the installation of the concrete slab; in particular, damage from any reinforcement mesh.
  • Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polarfoam SOYA HFO has shown ability to seal around penetrations of 100-mm CPVC, copper, concrete and cast iron pipes and 38-mm ABS pipes, without need for sealant. Other materials may require additional sealant (that is, polyethylene pipes).

 

 

Figure 1. Application of Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polarfoam SOYA HFO for radon control beneath concrete slab, with geotextile/100 mm gravel or without geotextile/118 to 124 mm gravel bed.

  1. Exterior wall dampproofing
  2. Concrete foundation wall
  3. Concrete floor slab
  4. Minimum 38-mm thick Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polarfoam SOYA HFO (CCMC 14078-L)
  5. 100 mm granular fill with geotextile, or 118 to 124 mm granular fill
  6. Original soil

Figure 2. Application of Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polarfoam SOYA HFO for radon control beneath concrete slab, with geotextile/100 mm gravel or without geotextile/118 to 124 mm gravel bed.

  1. Centre of floor slab
  2. Concrete floor slab
  3. Minimum 38-mm thick Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polarfoam SOYA HFO (CCMC 14078-L)
  4. 100 mm granular fill with geotextile, or 118 to 124 mm granular fill
  5. Exhaust pipe

 

  Technical information

This evaluation is based on demonstrated conformance with the following criteria:

Evaluation requirements
Criteria number Criteria name
CCMC-TG-072623.01-15CCMC Technical Guide for Medium Density (MD) Spray Polyurethane Foam Insulation (SPUF) for Soil Gas (Radon) Control beneath Concrete Slabs-on-Ground

The Report Holder has submitted technical documentation for CCMC’s evaluation. Testing was conducted at laboratories recognized by CCMC. The corresponding technical evidence for this product is summarized below.

Performance requirementsThe following were the key performance requirements for the evaluation:
  1. Material qualification: Medium-density spray polyurethane foam (SPUF) complying with CAN/ULC-S705.1, and installation as per CAN/ULC-S705.2. Confirmed through possession of active CCMC Listing;
  2. Air barrier system: The air barrier system for floors-on-ground qualification through testing. The NBC 2015 benchmark is 6-mil polyethylene as per Sentence 9.25.3.6.(1) of Division B of the NBC 2015 and;
  3. Soil gas barrier: The barrier performance against soil gas, specifically radon, based on qualification testing, small-scale and large-scale. The NBC 2015 benchmark is 6-mil polyethylene as per Sentence 9.13.4.2.(1) of Division B of the NBC 2015, referring to Sentence 9.25.3.6.(1) and;
  4. Resistance to mechanical damage: Repeat small-scale radon-barrier testing with indented SPUF by simulated concrete pour/workman load damage.
Table 1. Material qualification
SPUF product CAN/ULC-S705.1 compliance Thermal insulation in field (CAN/ULC-S705.2) site quality assurance program (SQAP) Radon barrier in field Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polar Foam SOYA HFO site quality assurance program (SQAP)
CCMC 14078-L (Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polar Foam SOYA HFO) Huntsman Building Solutions (Canada) Inc.-trained and Caliber-certified installers Huntsman Building Solutions (Canada) Inc.-trained and Caliber-certified installers

 

Table 2. Air barrier system performance
Material Test procedure Unit Requirement Result
SPUF product CCMC 14078-L sealing around pipe penetrationsTable footnote (1) ASTM E 2178/E 2178M-13Table footnote (1) L/(s∙m2) 0.02Table footnote (2) 0.0041 – 0.0045Table footnote (3)
6-mil polyethylene NBC 2015 Table A-9.25.5.1.Table footnote (1) L/(s∙m2) NBC-acceptable solution benchmark negligible

 

Table 3. Radon barrier performance for Huntsman Building Solutions (Canada) Inc. SPUF product CCMC 14078-L at 38-mm thickness
Property Unit RequirementTable footnote (1) Result
Small-scale tests
Radon diffusion coefficient (D)Table footnote (2) m2/s < 2.19 × 10-11 m2/s
6-mil polyethylene NBC benchmark
negligibleTable footnote (3)
Radon resistance (Rradon)Table footnote (2) s/m ≥ 6.96 × 106 s/m
6-mil polyethylene NBC benchmark
Table footnote (3)
Radon diffusion coefficient (D) after mechanical damage m2/s < 2.19 × 10-11 m2/s
6-mil polyethylene NBC benchmark
Table footnote (3)Table footnote (4)
Radon resistance (Rradon) after mechanical damage s/m ≥ 6.96 × 106 s/m
6-mil polyethylene NBC benchmark
Table footnote (3)Table footnote (4)
Large-scale tests
Radon infiltration (Heatlok® SOYA HFO, Airmetic® SOYA HFO, Polar Foam SOYA HFO and floor assembly)Table footnote (5) % < 37.6 % (RnR/RnD)Table footnote (6)
6-mil polyethylene NBC benchmark
3.0

 

 NRC Construction Research Centre Radon Testing Facilities

(1) Small-scale Tests Radon Diffusion Test Chamber (RDTC)

Schematic of Radon Diffusion Test Chamber
Figure 3. Schematic of RDTC
  1. Receiving compartment
  2. Radon monitor
  3. Test sample
  4. Dosing compartment
  5. Radon source

 

(2) Large-scale Tests Radon Infiltration Building Envelope Test Systems (RIBETS)

Conceptual design of the Radon Infiltration Building Envelope Test Systems
Figure 4. Conceptual design of the RIBETS
  1. Sub-slab radon (Rn) exhaust stack (100 mm PVC pipe)
  2. Make-up air stack
  3. Exhaust stack
  4. Control damper
  5. In-line fan
  6. Baseboard heater
  7. Radon source
  8. Dosing compartment
  9. Receiving compartment
  10. Concrete pad
  11. Perforated stainless steel plate
  12. Gravel (100 mm), specification as per NBC 2015 and NBC 2020
  13. Air barrier (6-mil polyethylene or spray foam products)
  14. Concrete slab (101.6 mm)
  15. Copper tubing for pressure measurement

Administrative information

Use of Canadian Construction Materials Centre (CCMC) assessments

This assessment must be read in the context of the entire CCMC Registry of Product Assessments, any applicable building code or by-law requirements, and/or any other regulatory requirements (for example, the Canada Consumer Product Safety Act, the Canadian Environmental Protection Act, etc.).

It is the responsibility of the user to confirm that the assessment they are using is current and has not been withdrawn or superseded by a later version on the CCMC Registry of Product Assessments.

Disclaimer

The National Research Council of Canada (NRC) has evaluated only the characteristics of the specific product described herein. The information and opinions in this evaluation are directed to those who have the appropriate degree of experience to use and apply its contents (such as authorities having jurisdiction, design professionals and specifiers). This evaluation is valid when the product is used as part of permitted construction, respecting all conditions and limitations stated in the evaluation, and in accordance with applicable building codes and by-laws.

This evaluation is provided without representation, warranty or guarantee of any kind, expressed or implied, and the NRC provides no endorsement for any evaluated product. The NRC accepts no responsibility whatsoever arising in any way from any and all use of or reliance on the information contained herein or the use of any evaluated product. The NRC is not undertaking to render professional or other services on behalf of any person or entity nor to perform any duty owed by any person or entity to another person or entity.

Language

Une version française de ce document est disponible.
In the case of any discrepancy between the English and French version of this document, the English version shall prevail.

Copyright

© His Majesty the King in Right of Canada, as represented by the National Research Council of Canada, 2023

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, without the prior written permission of the CCMC.

Date modified: