Language selection

Search


[CCMC 14205-R] CCMC Canadian code compliance evaluation

In most jurisdictions this document is sufficient evidence for approval by Canadian authorities.

Learn more about CCMC recognition Look for the trusted CCMC mark on products to verify compliance.

Compliance opinion

It is the opinion of the Canadian Construction Materials Centre that the evaluated product, when used as vapour barrier and a thermal insulation installed in conjunction with a furred air space in enclosed foundation walls in accordance with the conditions and limitations stated in this evaluation, complies with the following codes:

National Building Code of Canada 2015

ID Code provision Solution type
09-25-02-02-00-0-009.25.2.2.(1) Except as required in Sentence 9.25.2.2. ...Alternative
09-25-02-02-01-d-009.25.2.2.(1)(d) Insulation MaterialsAcceptable
09-25-04-02-00-0-009.25.4.2.(4) Membrane-type vapour barriers other than ...Alternative
09-25-04-02-00-0-009.25.4.2.(1) Vapour barriers shall have a permeance n ...Acceptable
09-25-04-03-00-0-009.25.4.3. Installation of Vapour BarriersAcceptable
09-36-02-02-04-b-009.36.2.2.(4)(b) Determination of Thermal Characteristics of Materials, Components and AssembliesAlternative
09-36-02-08-00-0-009.36.2.8. Thermal Characteristics of Building Assemblies Below-Gradeor in Contact with the GroundAlternative

National Building Code of Canada 2020

ID Code provision Solution type
92502020000009.25.2.2.(1) Except as required in Sentence 9.25.2.2. ...Alternative
92502020000009.25.2.2.(1)(d) ULC CAN/ULC-S701.1:2017 Standard for The ...Acceptable
92504020000009.25.4.2.(1) Except as provided in Sentence 9.25.4.2. ...Acceptable
92504020000009.25.4.2.(5) Membrane-type vapour barriers other than ...Alternative
92504030000009.25.4.3. Installation of Vapour BarriersAcceptable
93602020000009.36.2.2.(4)(b) laboratory tests performed in accordance ...Alternative
93602080000009.36.2.8. Thermal Characteristics of Building Assemblies Below-Gradeor in Contact with the GroundAlternative

Ontario Building Code

Ruling No. 22-01-370 (14205-R) authorizing the use of this product in Ontario, subject to the terms and conditions contained in the Ruling, was made by the Minister of Municipal Affairs and Housing on 2022-06-09 pursuant to s.29 of the Building Code Act, 1992 (see Ruling for terms and conditions). This Ruling is subject to periodic revisions and updates.


The above opinion(s) is/are based on the evaluation by the CCMC of technical evidence provided by the evaluation holder, and is bound by the stated conditions and limitations. For the benefit of the user, a summary of the technical information that forms the basis of this evaluation has been included.

Product information

Product name

NovoFoil®

Product description

The product consists of a 76.2-mm-thick Type 1, moulded, expanded polystyrene (EPS) insulation board, which is laminated on one side with a facer of aluminized kraft paper with low-emissivity (low-E) characteristics. There is no text or logo printed on the low-E facer.

The product is nailed to the interior side of a 203.2-mm-thick poured concrete foundation wall with its low-E material facing a furred air space assembly (i.e., air cavity, furring and gypsum board interior finish), and the joints of the product are sealed with 50-mm-wide aluminum tape. Three evaluated foundation wall configurations are presented in Figure 1, Figure 2 and Figure 3, which outline the wood furring size, installation orientation and spacing on centre (o.c.).

Manufacturing plant

This evaluation is valid only for products produced at the following plant:

Product nameManufacturing plant
Granby, QC, CA
NovoFoil®Product evaluated by the CCMC

Product evaluated by the CCMC Indicates that the product from this manufacturing facility has been evaluated by the CCMC

  Conditions and limitations

The CCMC’s compliance opinion is bound by this product being used in accordance with the conditions and limitations set out below.


Note: Should additional insulation material be added to the above-specified wall assemblies, testing or numerical modeling must be conducted to accurately assess the overall thermal resistance of the modified wall assembly. The thermal resistance provided by the additional insulation cannot be added algebraically to the published thermal resistance of the wall assembly.


  • The wall configurations specified in Results of modeling the thermal resistance values for the wall assembly 1Results of modeling the thermal resistance values for the wall assembly 2 and Results of modeling the thermal resistance values for the wall assembly 3 must meet the requirements for air barriers stated in Subsection 9.25.3., Air Barrier Systems, of Division B of the NBC 2015. The product must be installed in conjunction with the Les Plastiques Cellulaires Polyform Inc. proprietary air barrier system, which must be approved by the building official or evaluated by the CCMC.
  • The furred air space assembly must be enclosed by a 12.7-mm-thick gypsum board interior finish conforming to Subsection 9.29.5., Gypsum Board Finish (Taped Joints), of Division B of the NBC 2015. The air space must also be sealed at the interior finish to prevent any air exchange between the furred air space and the interior space. Sealing the air space at the perimeter of the wall, around outlets, etc., must be carried out in accordance with the manufacturer’s installation instructions.
  • All ends and edges of the gypsum board must occur over furring members or joints must be taped.
  • The heat transfer, vapour diffusion and air barrier control details between the floor joists at the rim board must meet the requirements of Section 9.25, Heat Transfer, Air Leakage and Condensation Control, of Division B of the NBC 2015.
  • The concrete footing must be installed below the frost level in compliance with the requirements of the local jurisdiction.
  • Where applicable, the concealed spaces created by the furred air space assembly must include fire blocks complying with Subsection 9.10.16., Fire Blocks, of Division B of the NBC 2015.
  • Product packaging must be identified with the manufacturer’s name or logo and the phrase “CCMC 14205-R.”

  Technical information

This evaluation is based on demonstrated conformance with the following criteria:

Evaluation requirements
Criteria number Criteria name
CCMC-TG-072131.03-15CCMC Technical Guide for Foundation Wall System with Low Emissivity Material and Furred-Airspace Assembly
CCMC-TG-072131.03-20CCMC Technical Guide for Foundation Wall System with Low Emissivity Material and Furred-Airspace Assembly

The evaluation holder has submitted technical documentation for the CCMC’s evaluation. Modeling was conducted by experts recognized by the CCMC. The corresponding technical evidence for this product is summarized below.

Material requirements

 

The NovoFoil® thermal insulation board used within the wall assemblies shown in Figure 1Figure 2, and Figure 3 conforms to CAN/ULC-S701-11, “Standard for Thermal Insulation, Polystyrene, Boards and Pipe Covering,” Type I, as presented in the table below:

Table 1. Results of testing the material requirements of the insulation board
PropertyTable footnote (1) Unit Requirement Result
Thermal resistance of a 25-mm-thick specimen (EPS only)  m2·°C/W 0.65 Pass
Water vapour permeance for a 25-mm-thick specimen ng/(Pa·s·m2) ≤ 300 Pass
Dimensional stability % linear change 1.5 Pass
Flexural strength kPa 170 Pass
Water absorption % by volume 6.0 Pass
Compressive strength kPa 70 Pass
Limiting oxygen index % 24 Pass

 

Table 2. Results of testing the material requirements of the low-E facer
Property Unit Requirement Result
Foil conforms to CAN/CGSB-51.33-M89 - Pass Pass: Type 1
Emissivity - Report value 0.07
Water vapour permeance conforms to
ASTM E 96/E 96M-05 (desiccant method)
ng/(Pa·s·m2) ≤ 60 1.0
Adhesion strength (peel force) N/mm Report value 114.9

 

Table 3. Results of testing the durability requirements of the low-E facer
Property Unit Requirement Result
Emissivity after weathering and heat aging % Max. 5% higher than
original value
Pass (0.06)
Water vapour permeance after weathering and heat aging ng/(Pa·s·m2) ≤ 60 1.0
Adhesion strength after weathering and heat aging % ≥ 85% of original value (105.3 N/mm)
Performance requirements

Heat transfer control (NovoFoil® board with a furred air space assembly)

The effective thermal resistance of the manufacturer’s designated wall assemblies 1, 2 and 3 shown in Figure 1Figure 2 and Figure 3 was determined based on numerical heat transfer simulations using COMSOL Multiphysics® for demonstrating compliance with Section 9.36, Energy Efficiency, of Division B of the NBC 2015.

Parameters used for the simulations (modeling)

Simulations were conducted using an indoor air temperature of 21±1°C and an outdoor air temperature of −18±1°C. These temperature parameters comply with the requirements of Section 9.36 of the NBC 2015. The simulations used 0.6 for the emissivity of the facer (result after aging and weathering) and the measured temperature-dependent thermal conductivity of the NovoFoil®. The thermal conductivity was determined as a linear fit of thermal resistance versus temperature, based on testing in compliance with ASTM C 518, “Standard Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus,” at mean temperatures of 24°C, 10°C, 4°C, −4°C, and −7.5°C.

Requirements of Article 9.36.2.8. of the NBC 2015

For compliance with Article 9.36.2.8., the minimum effective thermal resistance values for foundation walls in buildings for climate locations with heating degree-days (HDD) corresponding to Zone 4 (HDD < 3 000), Zone 5 (HDD between 3 000 and 3 999), and Zone 6 (HDD between 4 000 and 4 999) are presented in the table below. The minimum requirements apply for buildings with and without heat-recovery ventilators.

Table 4. Minimum effective design thermal resistance requirements and performance – Article 9.36.2.8. of the NBC 2015
Property Unit Requirements ResultTable footnote (1)Table footnote (2)
Zone 4 Zone 5 Zone 6
Minimum effective
thermal resistance
of wall assembly
wall assembly 1 (Figure 1) (m2·K)/W 1.99 2.98 2.98 Pass
wall assembly 2 (Figure 2) Pass
wall assembly 3 (Figure 3) Pass

 

 

Table 5. Results of modeling the thermal resistance values for the wall assembly 1
Property Unit Requirement Result
k1Table footnote (1) k2Table footnote (1)
Room-side air temperature °C Report value 21 21
Weather-side air temperature °C Report value −18 −18
Thermal resistance of the wallTable footnote (2)Table footnote (3) (m2·K)/W Report value 3.06 2.99
Design thermal resistance of the wallTable footnote (3)Table footnote (4) (m2·K)/W Table footnote (5) 3.21 3.14

 

isometric drawing of assembly 1

Figure 1. NovoFoil® adjacent to the furred air space assembly installed within the wall assembly 1:

  1. Concrete wall (203.2 mm (8 in.) thick)
  2. Aluminum tape (50 mm (2 in.) wide)
  3. NovoFoil® Type 1 (76.2 mm (3 in.) thick) with low-E material facing furred air space
  4. Wood furring (19.1 mm × 63.5 mm (1 × 3)) installed vertically at 609.6 mm (24 in.) on centre (o.c.)
  5. Gypsum board (12.7 mm (1/2 in.) thick) installed vertically

Note: There is an air space of 19.1 mm (3/4 in.) between the polystyrene board (NovoFoil®) and the gypsum board.

 

Table 6. Results of modeling the thermal resistance values for the wall assembly 2
Property Unit Requirement Result
k1Table footnote (1) k2Table footnote (1)
Room-side air temperature °C Report value 21 21
Weather-side air temperature °C Report value −18 −18
Thermal resistance of the wallTable footnote (2)Table footnote (3) (m2·K)/W Report value 3.18 3.11
Design thermal resistance of the wallTable footnote (3)Table footnote (4) (m2·K)/W Table footnote (5) 3.33 3.26

 

isometric drawing of assembly 2

Figure 2. NovoFoil® adjacent to the furred air space assembly installed within the wall assembly 2:

  1. Concrete wall (203.2 mm (8 in.) thick)
  2. Aluminum tape (50 mm (2 in.) wide)
  3. NovoFoil® Type 1 (76.2 mm (3 in.) thick) with low-E material facing furred air space
  4. Wood furring (38.1 mm × 63.5 mm (2 × 3)) installed vertically at 609.6 mm (24 in.) on centre (o.c.)
  5. Gypsum board (12.7 mm (1/2 in.) thick) installed vertically

Note: There is an air space of 63.5 mm (2 1/2 in.) between the polystyrene board (NovoFoil®) and the gypsum board.

 

 

Table 7. Results of modeling the thermal resistance values for the wall assembly 3
Property Unit Requirement Result
k1Table footnote (1) k2Table footnote (1)
Room-side air temperature °C Report value 21 21
Weather-side air temperature °C Report value −18 −18
Thermal resistance of the wallTable footnote (2)Table footnote (3) (m2·K)/W Report value 3.10 3.02
Design thermal resistance of the wallTable footnote (3)Table footnote (4) (m2·K)/W Table footnote (5) 3.25 3.17
Additional data

Data in this section does not form part of the CCMC's Code compliance opinion.

Heat transfer control (NovoFoil® board with a furred air space assembly)

The following data are provided for comparison purposes with the requirements of the Novoclimat - Small Multiple-Unit Building (Novoclimat) program only. Novoclimat is a program administered by the Québec Ministry of Energy and Natural Resources. The latest requirements were issued on January 1, 2021.

Parmeters used for the simulations

The effective thermal resistance of the manufacturer’s designated wall assemblies 1, 2 and 3 shown in Figure 1Figure 2 and Figure 3 was determined based on numerical heat transfer simulations using COMSOL Multiphysics®. Simulations were conducted using an indoor air temperature of 21±1°C and an outdoor air temperature of −35±1°C. These temperature parameters comply with the Novoclimat requirements. The simulations used 0.6 for the emissivity of the facer (result after aging and weathering) and the measured temperature-dependent thermal conductivity of the NovoFoil®. The thermal conductivity was determined as a linear fit of thermal resistance versus temperature based on testing in compliance with ASTM C 518 at mean temperatures of 24°C, 10°C, 4°C, −4°C and −7.5°C.

Novoclimat requirements

For compliance with Novoclimat, the minimum effective thermal resistance values for foundation walls in buildings for climate locations with heating degree-days (HDD) < 6 000 are presented in the table below. The minimum requirements apply to buildings with heat-recovery ventilators.

Table 8. Minimum effective thermal resistance requirements – Novoclimat
Property Unit Requirement
zone HDD < 6 000
ResultsTable footnote (1)Table footnote (2)
Minimum effective
thermal resistance
of the wall assembly
wall assembly 1 (Figure 1) (m2·K)/W 3.17 Pass
wall assembly 2 (Figure 2) Pass
wall assembly 3 (Figure 3) Pass

 

 

Table 9. Results of modeling the thermal resistance values for the wall assembly 1
Property Unit Requirement Result
k1Table footnote (1) k2Table footnote (1)
Room-side air temperature °C Report value 21 21
Weather-side air temperature °C Report value −35 −35
Thermal resistance of the wallTable footnote (2)Table footnote (3) (m2·K)/W Report value 3.15 3.09
Design thermal resistance of the wallTable footnote (3)Table footnote (4) (m2·K)/W Table footnote (5) 3.30 3.24

 

 

Table 10. Results of modeling the thermal resistance values for the wall assembly 2
Property Unit Requirement Result
k1Table footnote (1) k2Table footnote (1)
Room-side air temperature °C Report value 21 21
Weather-side air temperature °C Report value −35 −35
Thermal resistance of the wallTable footnote (2)Table footnote (3) (m2·K)/W Report value 3.25 3.18
Design thermal resistance of the wallTable footnote (3)Table footnote (4) (m2·K)/W Table footnote (5) 3.40 3.33

 

 

Table 11. Results of modeling the thermal resistance values for the wall assembly 3
Property Unit Requirement Result
k1Table footnote (1) k2Table footnote (1)
Room-side air temperature °C Report value 21 21
Weather-side air temperature °C Report value −35 −35
Thermal resistance of the wallTable footnote (2)Table footnote (3) (m2·K)/W Report value 3.16 3.09
Design thermal resistance of the wallTable footnote (3)Table footnote (4) (m2·K)/W Table footnote (5) 3.31 3.24

Administrative information

Use of Canadian Construction Materials Centre (CCMC) assessments

This assessment must be read in the context of the entire CCMC Registry of Product Assessments, any applicable building code or by-law requirements, and/or any other regulatory requirements (for example, the Canada Consumer Product Safety Act, the Canadian Environmental Protection Act, etc.).

It is the responsibility of the user to confirm that the assessment they are using is current and has not been withdrawn or superseded by a later version on the CCMC Registry of Product Assessments.

Disclaimer

The National Research Council of Canada (NRC) has evaluated only the characteristics of the specific product described herein. The information and opinions in this evaluation are directed to those who have the appropriate degree of experience to use and apply its contents (such as authorities having jurisdiction, design professionals and specifiers). This evaluation is valid when the product is used as part of permitted construction, respecting all conditions and limitations stated in the evaluation, and in accordance with applicable building codes and by-laws.

This evaluation is provided without representation, warranty or guarantee of any kind, expressed or implied, and the NRC provides no endorsement for any evaluated product. The NRC accepts no responsibility whatsoever arising in any way from any and all use of or reliance on the information contained herein or the use of any evaluated product. The NRC is not undertaking to render professional or other services on behalf of any person or entity nor to perform any duty owed by any person or entity to another person or entity.

Language

Une version française de ce document est disponible.
In the case of any discrepancy between the English and French version of this document, the English version shall prevail.

Copyright

© His Majesty the King in Right of Canada, as represented by the National Research Council of Canada, 2024

All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, without the prior written permission of the CCMC.

Page details

From: National Research Council Canada

Date modified: