[CCMC 12416-R] CCMC Canadian code compliance evaluation
CCMC number: | 12416-R |
Status: | Active |
Issue date: | 1992-08-12 |
Modified date: | 2023-12-19 |
Evaluation holder: | Sto Canada Ltd.
1821 Albion Road, Unit 1–2 |
Product names: |
|
Compliance: | NBC 2015, NBC 2020, OBC |
Criteria: |
|
In most jurisdictions this document is sufficient evidence for approval by Canadian authorities.
Learn more about CCMC recognition Look for the trusted CCMC mark on products to verify compliance.Compliance opinion
It is the opinion of the Canadian Construction Materials Centre that the evaluated products, when used as exterior wall cladding designed to be a weather barrier and to provide thermal insulation in accordance with the conditions and limitations stated in this evaluation, comply with the following codes:
National Building Code of Canada 2015
ID | Code provision | Solution type |
---|---|---|
03-01-04-02-01-c-00 | 3.1.4.2.(1)(c) Protection of Foamed Plastics | Acceptable |
03-01-05-00-00-0-00 | 3.1.5.15(2)(a) Foamed Plastic Insulation | Acceptable |
03-01-05-05-00-0-00 | 3.1.5.5.(1) Except as provided in Sentences 3.1.5.5. ... | Acceptable |
03-02-03-08-01-b-00 | 3.2.3.8.(1)(b) Protection of Exterior Building Face | Acceptable |
05-06-01-01-00-0-00 | 5.6.1.1.(1) Except as provided in Sentence 5.6.1.1.( ... | Acceptable |
05-09-04-00-00-0-00 | 5.9.4. Exterior Insulation Finish Systems | Acceptable |
05-09-04-01-00-0-00 | 5.9.4.1.(1) Exterior insulation finish systems and t ... | Acceptable |
09-25-02-02-01-d-00 | 9.25.2.2.(1)(d) Insulation Materials | Acceptable |
09-27-01-01-00-0-00 | 9.27.1.1.(5) Where an exterior insulation finish syst ... | Acceptable |
09-27-02-01-00-0-00 | 9.27.2.1. Minimizing and Preventing Ingress and Damage | Acceptable |
09-27-02-02-01-e-00 | 9.27.2.2.(1)(e) Minimum Protection from Precipitation Ingress | Acceptable |
09-27-02-03-00-0-00 | 9.27.2.3.(1) Where walls required to provide protecti ... | Acceptable |
09-27-03-01-00-0-00 | 9.27.3.1. Elements of the Second Plane of Protection | Acceptable |
09-27-13-00-00-0-00 | 9.27.13. Exterior Insulation Finish Systems | Acceptable |
09-27-13-02-00-0-00 | 9.27.13.2.(1) The materials used in EIFS shall conform ... | Acceptable |
National Building Code of Canada 2020
ID | Code provision | Solution type |
---|---|---|
3.1.4.2. | 3.1.4.2.(1)(c) by any thermal barrier that meets the re ... | Acceptable |
3.1.5.12. | 3.1.5.12.(2) Combustible interior wall finishes, othe ... | Acceptable |
3.1.5.5. | 3.1.5.5.(1) Except as provided in Sentences 3.1.5.5. ... | Acceptable |
3.2.3.8. | 3.2.3.8.(1)(b) noncombustible material that complies wi ... | Acceptable |
5.6.1.1. | 5.6.1.1.(1) Except as provided in Sentence 5.6.1.1.( ... | Acceptable |
5.9.4. | 5.9.4. Exterior Insulation Finish Systems | Acceptable |
5.9.4.1. | 5.9.4.1.(1) Exterior insulation finish systems and t ... | Acceptable |
9.25.2.2. | 9.25.2.2.(1) Except as required in Sentence 9.25.2.2. ... | Acceptable |
9.27.1.1. | 9.27.1.1.(5) Where an exterior insulation finish syst ... | Acceptable |
9.27.14. | 9.27.14. Exterior Insulation Finish Systems | Acceptable |
9.27.14.2. | 9.27.14.2.(1) The materials used in EIFS shall conform ... | Acceptable |
9.27.2.1. | 9.27.2.1. Minimizing and Preventing Ingress and Damage | Acceptable |
9.27.2.2. | 9.27.2.2.(1) Except as provided in Sentence 9.27.2.2. ... | Acceptable |
9.27.2.3. | 9.27.2.3.(1) Where walls required to provide protecti ... | Acceptable |
9.27.3.1. | 9.27.3.1. Elements of the Second Plane of Protection | Acceptable |
Ontario Building Code
Ruling No. 95-03-022 (12416-R) authorizing the use of this product in Ontario, subject to the terms and conditions contained in the Ruling, was made by the Minister of Municipal Affairs and Housing on 1995-03-02 (revised 1998-05-15) pursuant to s.29 of the Building Code Act, 1992 (see Ruling for terms and conditions). This Ruling is subject to periodic revisions and updates.
The above opinion(s) is/are based on the evaluation by the CCMC of technical evidence provided by the evaluation holder, and is bound by the stated conditions and limitations. For the benefit of the user, a summary of the technical information that forms the basis of this evaluation has been included.
Product information
Product names
- StoTherm®ci Classic
- StoTherm®ci Essence
- StoTherm®ci Lotusan
Product description
The products are non-loadbearing exterior insulation and finish systems (EIFS) that can be assembled in panels under factory-controlled conditions, or field-applied. The systems are composed of the following key components:
- A water-resistive barrier (WRB);
- An adhesive;
- An insulation board; and
- A coating system (lamina).
Note: The lamina refers to all coats (base and finish) applied to the outer face of the insulation board with the glass-fibre mesh reinforcement.
The components of the systems are listed below.
Substrate
For applications falling under the scope of this Report, the substrate can be brick, masonry, monolithic concrete walls, and/or cementitious panels, glass mat surfaced gypsum boards, plywood or oriented strandboard (OSB) over wood or steel framing. Gaps between the sheathing boards of framed walls must not exceed 3.0 mm.
Water-resistive barrier (WRB)
The water resistive barrier (WRB) is a coating that is installed to provide, along with other built-in features, the second line of defence against water infiltration reaching the structure. The WRB must be applied in accordance with the product’s installation manuals.
In systems with a WRB, the continuity of the second plane of protection across joints and junctions at openings, penetrations and expansion joints must be maintained through the use of accessories such as self-adhering membranes, tapes, etc., as specified by the manufacturer, prior to the installation of these systems. Furthermore, in order to provide the intended level of protection against water infiltration, the WRB must be applied in two coats with sufficient time between applications to allow the first coat to cure before the second coat is applied.
The StoGuard® coating system consists of two components: Sto Gold Fill® with StoGuard® Mesh or Sto Detail Mesh and Sto Gold Coat®, which are fluid-applied over approved substrates to provide a monolithic air and moisture barrier:
- Sto Gold Fill® is a water-based, flexible, trowel-applied joint compound that bridges sheathing joints and protects rough openings.
- Sto Gold Coat® (81636) is a ready-mixed, water-based, flexible coating for direct application to vertical above-grade wall sheathing, concrete, and concrete masonry. Sto Gold Coat® (81636) is applied in a continuous layer over the substrate and wrapped around the framing and penetration to achieve a minimum wet thickness of 0.41 mm (16 mils).
Sto Flexyl is a grey polymer-modified coating that is supplied in 19-L pails and mixed on site with 50% by weight Type GU Portland cement. Sto Flexyl is applied in a continuous layer over the substrate and wrapped around the framing and penetration to achieve a minimum wet thickness of 1.5 mm.
Sto Watertight Coat is a two-component, polymer-modified coating that is supplied in 19-L pails. The wet component and grey or white powder component are mixed on-site. Sto Watertight Coat is applied in a continuous layer over the substrate and wrapped around the framing and penetration to achieve a minimum wet thickness of 1.5 mm.
Adhesive
Sto BTS® Plus is a one-component, polymer-modified, cement-based dry powder material used as an adhesive and supplied in 21.3-kg bags. Each bag is mixed with 4.7 L to 6.2 L of clean water. Sto BTS® Plus is applied as an adhesive to the inward surface of the Sto insulation board using the appropriate notched trowel. For smooth substrates such as sheathing, use a stainless steel trowel with U-shaped notches measuring 13 mm × 13 mm at 64 mm on centre (o.c.). For uneven substrates such as some types of concrete masonry, use a trowel with square notches measuring 16 mm × 16 mm at 32 mm o.c. As a base coat, the product is applied in a single continuous layer over the insulation board to achieve a minimum thickness of 1.6 mm.
Sto Primer/Adhesive-B is a one-component, polymer-modified, cement-based, dry powder material supplied in 23-kg bags. Each bag is mixed with 4.7 L to 6.2 L of clean water. Sto Primer/Adhesive-B is applied as an adhesive to the surface of the Sto Corp. insulation board using the appropriate notched trowel. For smooth substrates such as sheathing, use a trowel with U-shaped notches measuring 13 mm × 13 mm at 64 mm o.c. For uneven substrates such as some types of concrete masonry, use a trowel with square notches measuring 16 mm × 16 mm at 32 mm o.c., or apply the product directly to the substrate using Sto Corp.’s M-8 spray pump and trowel with the appropriate notched trowel. As a base coat, the product is applied in a single continuous layer over the insulation board to achieve a minimum thickness of 1.6 mm.
Note: Adhesives are used for bonding the insulation to the substrate coated with the WRB. They are, in general, available in the following forms: a dry powder mix that requires the addition of water on-site, a wet paste that requires the addition of cement on-site, and a form that does not require any additives. Certain adhesives are also used as base coats.
Insulation
Sto EPS Insulation Board and Sto ProD EPS Insulation Board are manufactured and packaged by Sto Corp., qualified and licensed manufacturers/molders. The expanded polystyrene foam insulation boards are aged by air for a minimum of five weeks or kiln-dried.
Sto EPS Insulation Board is a typical flat EPS board.
Sto ProD EPS Insulation Board has drainage pathways cut into the insulation that conform with Clause 9.27.13.1.(1)(b) of Division B of the NBC 2015.
The two insulation boards must conform to the following:
- CAN/ULC-S701-11, “Standard for Thermal Insulation, Polystyrene, Boards and Pipe Covering,” Type 1 or Type 2;
- Minimum board thickness: 25 mm;
- Maximum board thickness:
- as designed, when used in combustible construction;
- 165 mm, when used in noncombustible construction meeting Article 3.1.5.5 of Division B of the NBC 2015 for StoTherm Systems and when applied over minimum 2 × 6 wood framing covered with a minimum 12.7-mm gypsum sheathing; and
- 165 mm, when used in noncombustible construction meeting Clause 3.2.3.8.(1)(b) of Division B of the NBC 2015 for StoTherm Systems;
- Maximum board size: 600 mm × 1 200 mm;
- Nominal density: 16 kg/m3; and
- Flame-spread rating: 25–500, per CAN/ULC-S102.2-11, “Standard Method of Test for Surface Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies.”
Synthetic coating system (lamina)
The synthetic coating system (lamina) consists of the reinforcing mesh, which is embedded with the base coat, a primer and a finish coat.
Base coats
When Sto BTS® Plus Sto Primer/Adhesive-B (see Adhesive) is used as a base coat, it is applied with a stainless-steel trowel to the entire surface of the insulation to a uniform nominal dry-rendered thickness of 1.6 mm.
Note: The required thickness of the base coat depends on the number of layers and the type of reinforcing mesh used. The base coat is thicker when more than one layer of reinforcing mesh is incorporated into the lamina. Ultimately, it must be thick enough to fully embed the reinforcing mesh into the base coat with no mesh colour visible.
Reinforcing mesh
The reinforcing mesh is an alkali-resistant, interwoven glass-fibre reinforcing fabric having a minimum 142 g/m2 nominal weight that is used with the Sto Corp. base coats and the Sto Flexyl coating. The mesh is yellow or white (where noted) and available in 107-mm, 240-mm or 970-mm wide rolls. It is available in six grades of strength:
- Sto Detail Mesh: 142 g/m2, 240 mm wide
- Sto Mesh: 153 g/m2, 970 mm wide
- Sto 6oz Mesh: 203 g/m2, 970 mm wide
- Sto Intermediate: 373 g/m2, 970 mm wide
- Sto Armor Mat: 508 g/m2, 970 mm wide
- Sto Armor Mat XX: 678 g/m2, 970 mm wide
- StoGuard® Mesh: 142 g/m2, 107 mm and 240 mm wide
Primers
Sto Primer Smooth is a water-based acrylic smooth primer that provides uniform substrate absorption and finish colour and is supplied in 19-L pails. Sto Primer Smooth is applied by brush, roller or spray to the dry base coat and provides an approximately 0.1–0.15 mm wet thickness.
Sto Primer Creativ is a water-based acrylic primer supplied in 19-L pails. Sto Primer Creativ is applied by brush, roller or spray to the dry base coat and provides an approximately 0.1–0.15 mm wet thickness.
Sto Primer Sanded is a water-based acrylic sanded primer that provides uniform substrate absorption and finish colour and is supplied in 19-L pails. Sto Primer Sanded is applied by brush, roller or spray to the dry base coat and provides an approximately 0.1–0.15 mm wet thickness.
Note: Primer is typically required for spray- or roller-applied finishes.
Finish coats
Stolit® Lotusan is an acrylic-based textured finish coat with graded marble aggregate supplied in 19-L pails. It is factory- or store-tinted to the desired colour. Finished thickness is 1.0–1.5 mm, depending on the texture selected.
Stolit® is a ready-mix, acrylic-based, textured emulsion finish coat supplied in 19-L pails. It is factory- or store-tinted to the desired colour. Stolit® is applied with a stainless-steel trowel or spray-applied to a 1.0–3.0 mm thickness, depending on the texture selected.
StoSilco® Lit is a ready-mix, acrylic-based, silicone-enhanced, textured emulsion finish coat supplied in 19-L pails. It is factory- or store-tinted to the desired colour. StoSilco® Lit is applied with a stainless-steel trowel or spray-applied to a 1.0–1.5 mm thickness, depending on the texture selected.
Sto Essence and Sto Element Finish is an acrylic-based textured finish coat with graded marble aggregate and DPR technology supplied in 19-L pails. It is factory- or store-tinted to the desired colour. Finished thickness is 1.0–1.5 mm, depending on the texture selected.
Sto exterior insulation and finish system (EIFS) elements
System | Distinctive system components | |||||
---|---|---|---|---|---|---|
Insulation | Intended substrate | Water-resistive barrier | Adhesive | Base coat | Finish coat | |
StoTherm®ci Lotusan | Sto EPS Insulation Board, Sto ProD EPS Insulation Board | Glass mat gypsum, cement board, concrete, masonry | StoGuard®, Sto Flexyl, Sto Watertight Coat | Sto BTS® Plus | Sto BTS® Plus | Stolit® Lotusan |
Plywood/OSB | StoGuard® | |||||
StoTherm®ci Classic | Sto EPS Insulation Board, Sto ProD EPS Insulation Board | Glass mat gypsum, cement board, concrete, masonry | StoGuard®, Sto Flexyl, Sto Watertight Coat | Sto BTS® Plus | Sto BTS® Plus | Stolit®, StoSilco® Lit |
Plywood/OSB | StoGuard® | |||||
StoTherm®ci Essence | Sto EPS Insulation Board, Sto ProD EPS Insulation Board | Glass mat gypsum, cement board, concrete, masonry | StoGuard®, Sto Flexyl, Sto Watertight Coat | Sto Primer/Adhesive-B | Sto Primer-/ Adhesive-B | Sto Essence Finish or Sto Element Finish |
Plywood/OSB | StoGuard® |
Manufacturing plants
This evaluation is limited to products produced at the following plants:
Product names | Manufacturing plants | ||
---|---|---|---|
Atlanta, GA, US | Glendale, AZ, US | Rutland, VT, US | |
StoTherm®ci Classic | Product evaluated by the CCMC | Product evaluated by the CCMC | Product evaluated by the CCMC |
StoTherm®ci Essence | Product evaluated by the CCMC | Product evaluated by the CCMC | Product evaluated by the CCMC |
StoTherm®ci Lotusan | Product evaluated by the CCMC | Product evaluated by the CCMC | Product evaluated by the CCMC |
Product evaluated by the CCMC Indicates that the product from this manufacturing facility has been evaluated by the CCMC
Conditions and limitations
The CCMC’s compliance opinion is bound by this product being used in accordance with the conditions and limitations set out below.
- The product is intended for use as an exterior wall cladding on buildings falling under the scope of Parts 5 and 9 of the NBC 2015 and the NBC 2020.
- When used in existing buildings, the applicable or the relevant elements of the existing buildings must comply with the requirements of the NBC 2015 and the NBC 2020.
- The products are intended to be used as exterior insulation and finish wall systems (EIFS) applied directly to vertical brick, masonry or monolithic concrete walls, and/or cementitious, glass mat surfaced gypsum, plywood or OSB-sheathing boards installed over wood or steel framing.
- Gaps between the sheathing boards of framed walls must not exceed 3.0 mm.
- The products are acceptable for use on vertical walls. The systems are not acceptable for use on horizontal surfaces. (Note: The present limitation doesn’t include protected soffit applications.)
- When the products are part of a prefabricated panel system that incorporates structural components, the prefabricated panel system must be designed by a professional engineer or architect in accordance with the manufacturer’s criteria and the requirements of the NBC 2015 and the NBC 2020.
- The products are not suitable for use as a structural sheathing for bracing purposes.
- The products are not intended for use as a below-grade insulation and should terminate at least 200 mm above grade level.
- For buildings within the scope of Part 5 of Division B of the NBC 2015, the system shall be designed in accordance with the requirements of Article 5.9.4.1., Structural Loads, Heat Transfer, Air Leakage, Vapour Diffusion and Water Penetration, of the NBC 2015.
- For buildings within the scope of Part 5 of Division B of the NBC 2020, the system shall be designed in accordance with the requirements of Article 5.9.4.1., Structural Loads, Heat Transfer, Air Leakage, Vapour Diffusion and Water Penetration, of the NBC 2020.
- When used in coastal areas on residential occupancies that fall under the scope of Part 9 of Division B of the NBC 2015, the products must be installed in conjunction with a capillary break conforming to Sentence 9.27.2.2.(1)(e) of Division B of the NBC 2015. Coastal areas are defined in Sentence 9.27.2.2.(5) of Division B of the NBC 2015.
- When used in coastal areas on residential occupancies that fall under the scope of Part 9 of Division B of the NBC 2020, the products must be installed in conjunction with a capillary break conforming to Sentence 9.27.2.2.(1)(e) of Division B of the NBC 2020. Coastal areas are defined in Sentence 9.27.2.2.(5) of Division B of the NBC 2020.
- The WRB coating must be applied in two coats.
- The continuity of the second plane of protection across joints and junctions at openings, penetrations and expansion joints must be maintained through the use of accessories such as self-adhering membranes, tapes, etc., as specified by the manufacturer, prior to the installation of these systems.
- The use of the products with the adhesives indicated in the Sto Exterior Insulation and Finish System (EIFS) Elements table is limited to geographical areas where the wind-design value is Q50 < 1.0.
- When used on existing walls of sprinklered buildings or existing walls of the buildings with not more than 3 storeys, the possibility of moisture accumulation within the wall construction is mainly a function of 1) the ability of the wall assembly to deflect bulk water entry, and 2) the physical properties of the cladding being installed and its impact on the thermal, air leakage and vapour diffusion characteristics of the existing wall. The potential for moisture accumulation as a result of the addition of materials is very specific to the existing wall construction. Therefore, the installation must be in accordance with Appendix Note A-5.1.2.1(1), Application (Environmental Separation), of Division B of the NBC 2015 and the NBC 2020.
- For buildings within the scope of Part 9, Housing and Small Buildings, of the NBC 2015 and the NBC 2020, the design of the inboard/outboard insulation of the systems must be in accordance with the requirements of Section 9.25., Heat Transfer, Air Leakage and Condensation Control, of Division B of the NBC 2015and the NBC 2020.
- When the systems are used on existing walls, the addition of thermal insulation to existing exterior walls will increase the thermal efficiency and airtightness of the wall. Deficiencies in flashing and other elements in the building assembly, including mechanical systems, may result in detrimental effects of moisture accumulation as highlighted in Note A-9.25.2.4.(3), Loose-Fill Insulation in Existing Wood-Frame Walls, of Division B of the NBC 2015 and the NBC 2020. As a result, once the EIFS is installed, the existing exterior walls must meet the requirements of the NBC 2015 and the NBC 2020 for heat transfer, air leakage and condensation control.
- The products can provide additional thermal insulation to the wall assembly with no detrimental effects if properly designed and installed with knowledge of the existing wall configuration and performance.
- The products alone may not provide the full amount of the required wall insulation. The thermal resistance of the wall system must conform to the energy requirements of the applicable building code. The wall system may have to conform to the National Energy Code of Canada for Buildings.
- Before cutting into insulation boards, the polystyrene thermal insulation blocks must be aged for a minimum of five weeks or kiln-dried in accordance with the requirements of Section B2.1, “Aging,” of Annex B of CAN/ULC-S701, “Thermal Insulation, Polystyrene, Boards and Pipe Covering.”
- The polystyrene thermal insulation must be in conformance with the requirements of CAN/ULC-S701.
- The polystyrene thermal insulation boards must be cut from moulded blocks manufactured using 100% virgin raw materials.
- When used in combustible construction, the polystyrene insulation must be protected from the inside of the building in accordance with Clauses 3.1.4.2.(1)(c) and 9.10.17.10.(1)(c), Protection of Foamed Plastics, of Division B of the NBC 2015 and the NBC 2020.
- When used in noncombustible constructions, the polystyrene insulation must be protected from the inside of the building in accordance with Sentences 3.1.5.15.(2) and (3), Foamed Plastic Insulation, of Division B of the NBC 2015 and the NBC 2020.
- Where allowed by the Code through conformance to Sentence 3.1.5.5.(1), Combustible Cladding on Exterior Walls, of Division B of the NBC 2015 and the NBC 2020, “StoTherm®ci Lotusan,” “StoThetm®ci Classic” and “StoTherm®ci Essence” are acceptable for use on buildings required to be of noncombustible construction, where not more than three storeys in height if unsprinklered, and to an unlimited number of storeys if sprinklered, provided the interior surfaces of the wall assembly are protected by a thermal barrier conforming to Article 3.1.5.15., Foamed Plastic Insulation, of Division B of the NBC 2015 and the NBC 2020. For a detailed description of the compliance of “StoTherm®ci Lotusan,” “StoThetm®ci Classic” and “StoTherm®ci Essence” to the requirements of Sentence 3.1.5.5.(1) of Division B of the NBC 2015 and the NBC 2020, please refer to Intertek SPEC ID: 18818, Design No. STO/WDEIFS 25-01 Sto Category 1 Design Listing (please note that the wall assembly may include the use of wood-framing under some certain conditions , please refer to the Intertek fire listing for those conditions).
- Where allowed by the Code through conformance to Clause 3.2.3.8.(1)(b) of Division B of the NBC 2015 and the NBC 2020, “StoTherm®ci Lotusan,” “StoThetm®ci Classic” and “StoTherm®ci Essence” are acceptable for use in the exposed face of buildings required to be of combustible or noncombustible construction, provided the interior surfaces of the wall assembly are protected by a thermal barrier conforming to Article 3.1.5.15. of Division B of the NBC 2015 and the NBC 2020. For a detailed description of the compliance of “StoTherm®ci Lotusan,” “StoThetm®ci Classic” and “StoTherm®ci Essence” to the requirements of Clause 3.2.3.8.(1)(b) of Division B of the NBC 2015 and the NBC 2020, please refer to Intertek SPEC ID: 18188 Design No. STO/WDEIFS 15-01 Category 2 Design Listing (Please note that back-up wall assemblies covered by design listing do not include wood framing and wood sheathings and extend to non-combustible substrates only (steel stud over sheathings such as gypsum board, concrete, masonry and ICF)).
- The systems should be kept at least 50 mm or the distance required in applicable building regulations and safety codes from heat-emitting devices such as recessed light fixtures and chimneys.
- NBC 2015 and NBC 2020 requirements regarding fire stops must be implemented.
- The polystyrene thermal insulation must have a flame-spread rating of not more than 500 when tested in accordance with the requirements of CAN/ULC-S102.2-11, “Test for Surface Burning Characteristics of Flooring, Floor Coverings, and Miscellaneous Materials and Assemblies.”
- Movement joints are required to accommodate expansion and contraction of building materials due to thermal changes, moisture, wind, gravity, vibration and seismic activity. Movement joints in the cladding must be used in the following situations:
- at joints that occur in the substrate;
- at any abutment of the system with other materials;
- where changes in substrate might create deflection or movement;
- where significant structural movement occurs;
- where deflections in excess of L/240 are expected; and
- at the floor line in wood-frame construction (this may not be required where fully-engineered framing and floor systems are used)
- Closed-cell backer rods should be used at expansion joints so that the low-modulus sealant can be installed as per the seal
Technical information
This evaluation is based on demonstrated conformance with the following criteria:
Criteria number | Criteria name |
---|---|
CAN/ULC-S716.1-12 | Exterior Insulation and Finish Systems (EIFS) – Materials and Systems |
CCMC-TG-072413.01-15B | CCMC Technical Guide for Exterior Insulation and Finish Systems (EIFS) Class PB |
CCMC-TG-072413.01-20B | CCMC Technical Guide for Exterior Insulation Finish Systems |
The evaluation holder has submitted technical documentation for the CCMC’s evaluation. Testing was conducted at laboratories recognized by the CCMC. The corresponding technical evidence for this product is summarized below.
Material characterization
Property | Unit | Requirement | Result |
---|---|---|---|
WRB (StoGuard®) |
% |
Report value |
|
Sto Gold Fill® | 75.4 | ||
Sto Gold Coat® (81636) | 62.8 | ||
WRB (Sto Flexyl) | 97.2 | ||
WRB (Sto Watertight Coat) | 52.2 | ||
Adhesive/base coat (Sto BTS® Plus) | 95.1 | ||
Adhesive/base coat (Sto Primer/Adhesive-B) | 95.6 | ||
Finish coat (Stolit® Lotusan) | 62.8 | ||
Finish coat (Stolit®) | 64.2 | ||
Finish coat (StoSilco® Lit) | 64.7 | ||
Finish coat (Sto Essence Finish or Sto Element Finish) | 61.8 |
Property | Requirement | Result |
---|---|---|
WRB (StoGuard®) |
Report value |
Report on file |
Sto Gold Fill® | ||
Sto Gold Coat® (81636) | ||
WRB (Sto Flexyl) | ||
WRB (Sto Watertight Coat) | ||
Adhesive/base coat (Sto BTS® Plus) | ||
Adhesive/base coat (Sto Primer/Adhesive-B) | ||
Finish coat (Stolit® Lotusan) | ||
Finish coat (Stolit®) | ||
Finish coat (StoSilco® Lit) | ||
Finish coat (Sto Essence Finish or Sto Element Finish) |
Adhesion/cohesion bond
Property | Unit | Requirement: no detachment at bonding plane at | ResultTable footnote (1) | |
---|---|---|---|---|
StoGuard® to plywood | dry state |
MPa |
0.25 | 0.730 |
2-h drying | 0.08 | 0.447 | ||
7-d drying | 0.25 | 0.697 | ||
StoGuard® to OSB | dry state | 0.25 | 0.840 | |
2-h drying | 0.08 | 0.309 | ||
7-d drying | 0.25 | 0.713 |
Property | Unit | Requirement: no detachment at bonding plane at | Result | |
---|---|---|---|---|
StoGuard® to cement board | dry state |
MPa |
0.25 | 0.960 |
2-h drying | 0.08 | 0.498 | ||
7-d drying | 0.25 | 0.691 | ||
StoGuard® to glass mat gypsum | dry state | 0.25 | 0.76 | |
2-h drying | 0.08 | 0.21 | ||
7-d drying | 0.25 | 0.34 | ||
Sto Flexyl to cement board | dry state | 0.25 | 0.613 | |
2-h drying | 0.08 | 0.419 | ||
7-d drying | 0.25 | 0.708 | ||
Sto Flexyl to glass mat gypsum | dry state | 0.25 | 0.397 | |
2-h drying | 0.08 | 0.125 | ||
7-d drying | 0.25 | 0.215 | ||
Sto Watertight coat to cement board | dry state | 0.25 | 0.613 | |
2-h drying | 0.08 | 0.419 | ||
7-d drying | 0.25 | 0.708 | ||
Sto Watertight coat to glass mat gypsum | dry state | 0.25 | 0.397 | |
2-h drying | 0.08 | 0.125 | ||
7-d drying | 0.28 | 0.215 |
Property | Unit | Requirement: no detachment at bonding plane at | Result | |
---|---|---|---|---|
StoGuard® to concrete | dry state | MPa | 0.25 | 0.455 |
2-h drying | 0.08 | 0.551 | ||
7-d drying | 0.25 | 0.475 |
Property | Unit | Requirement: no detachment at bonding plane at | Result | |
---|---|---|---|---|
Sto BTS® Plus to StoGuard® | dry state |
MPa |
0.25 | 0.251 |
2-h drying | 0.08 | 0.225 | ||
7-d drying | 0.25 | 0.428 | ||
Sto Primer/Adhesive-B to StoGuard® | dry state | 0.25 | 0.401 | |
2-h drying | 0.08 | 0.370 | ||
7-d drying | 0.25 | 0.447 | ||
Sto BTS® Plus to Sto Flexyl | dry state | 0.25 | 0.3 | |
2-h drying | 0.08 | 0.1 | ||
7-d drying | 0.25 | 0.3 | ||
Sto Primer/Adhesive-B to Sto Flexyl | dry state | 0.25 | 0.3 | |
2-h drying | 0.08 | 0.1 | ||
7-d drying | 0.25 | 0.3 | ||
Sto BTS® Plus to Sto Watertight Coat | dry state | 0.25 | 0.3 | |
2-h drying | 0.08 | 0.1 | ||
7-d drying | 0.25 | 0.3 | ||
Sto Primer/Adhesive-B to Sto Watertight Coat | dry state | 0.25 | 0.3 | |
2-h drying | 0.08 | 0.1 | ||
7-d drying | 0.25 | 0.3 |
Property | Unit | Requirement: no detachment at bonding plane at | Result | |
---|---|---|---|---|
Sto BTS® Plus to EPS | dry state |
MPa |
0.08 | 0.1 |
2-h drying | 0.08 | 0.1 | ||
7-d drying | 0.08 | 0.1 | ||
Sto Primer/Adhesive-B to EPS | dry state | 0.08 | 0.1 | |
2-h drying | 0.08 | 0.1 | ||
7-d drying | 0.08 | 0.1 |
Property | Unit | Requirement: no detachment at bonding plane at | Result | |
---|---|---|---|---|
Sto BTS® Plus/Stolit® to EPS | dry state |
MPa
|
0.1 | 0.221 |
2-h drying | 0.1 | 0.143 | ||
7-d drying | 0.1 | 0.214 |
Water vapour transmission
Property | Unit | Requirement | Result |
---|---|---|---|
StoGuard® over OSB |
ng/(Pa·s·m2) |
Report value |
156Table footnote (1) |
78Table footnote (2) | |||
StoGuard® over glass-mat gypsum | 321Table footnote (1) | ||
224Table footnote (2) | |||
Sto Flexyl over OSB | 56Table footnote (1) | ||
56Table footnote (2) | |||
Sto Flexyl over glass-mat gypsum | 187Table footnote (1) | ||
94Table footnote (2) | |||
Sto Watertight over OSB | 56Table footnote (1) | ||
56Table footnote (2) | |||
Sto Watertight over glass-mat gypsum | 187Table footnote (1) | ||
94Table footnote (2) |
Property | Unit | Requirement | Result |
---|---|---|---|
Sto BTS® Plus |
ng/(Pa·s·m2) |
Report value |
524 |
Sto Primer/Adhesive-B | 211.8 |
Property | Unit | Requirement | Sample no. | ResultTable footnote (1) | ||
---|---|---|---|---|---|---|
Uncoated | Coated with StoGuard® | |||||
WVT | OSB | ng/(Pa·s·m2) | Report WVT rate of plywood and OSB coated with a WRB and of uncoated plywood and OSB | 1 | 84.44 | 49.44 |
2 | 111.25 | 44.84 | ||||
3 | 86.74 | 44.30 | ||||
Average | 94.14 | 47.86 | ||||
plywood | 1 | 235.21 | 137.73 | |||
2 | 214.22 | 128.73 | ||||
3 | 226.96 | 122.48 | ||||
Average | 225.47 | 129.65 |
Water absorption
Property | Unit | Requirement | Result |
---|---|---|---|
Sto BTS® Plus |
% |
≤ 20% of the dry weight |
12.28 |
Sto Primer/Adhesive-B | 17.05 |
Property | Unit | Requirement | Result |
---|---|---|---|
StoGuard |
kg/(m2·s1/2) |
≤ 0.004 |
0.0005 |
Sto Watertight Coat | 0.0013 | ||
Sto Flexyl | 0.0013 |
Impermeability to water
Property | Unit | Requirement | Result |
---|---|---|---|
Sto BTS® Plus |
h |
No water penetration in less than 2 h |
Pass |
Sto Primer/Adhesive-B | Pass |
Water transmission resistance
Property | Unit | Requirement | Sample no. | Result |
---|---|---|---|---|
WTR | kg/m2·s | Five WRB-coated OSB specimens subjected to a 25-mm head of water must have a maximum average WTR rate of 2 × 10−7 kg/m2·s measured at 10 days | 1 | Table footnote (1) |
2 | 1.87 × 10−7 | |||
3 | 9.97 × 10−8 | |||
4 | 3.25 × 10−8 | |||
5 | 1.64 × 10−7 | |||
Average | 1.21 × 10−7 |
Property | Unit | Requirement | Sample No. | Result |
---|---|---|---|---|
WTR | kg/m2·s | Five WRB-coated plywood specimens subjected to a 25-mm head of water must have a maximum average WTR rate of 2 × 10−7 kg/m2·s measured at 10 days | 1 | Table footnote (1) |
2 | 5.64 × 10−7 | |||
3 | 2.27 × 10−8 | |||
4 | 1.80 × 10−8 | |||
5 | 1.11 × 10−7 | |||
Average | 1.79 × 10−7 |
Durability
Property | Requirement | Result |
---|---|---|
Mildew and fungus resistance of finish coat (Stolit® & StoSilco® Lit) | No growth | Pass |
Property | Adhesive material | Applied finish | Requirement | Result |
---|---|---|---|---|
Accelerated weathering resistance of lamina @ 2 000 hrs | Sto BTS® Plus | Stolit® Finish | No cracking, flaking or deleterious effects | Pass |
Property | Requirement | Result |
---|---|---|
Sto BTS® Plus/Stolit | No cracking, flaking or deleterious effects | Pass |
Sto (Primer/Adhesive)/(Stolit®) | Pass |
Property | Unit | Requirement | Result | |
---|---|---|---|---|
Pre-conditioning (drainage evaluation) | L | Report water quantity | introduced | 13.5 |
drained | 12.59 | |||
retained | 0.91 | |||
Environmental cycling (60 cycles) | - | No cracking, blistering or sagging of base coat and no detachment or crazing of finish coat | Pass | |
Adhesion bond strength after environmental cycling | MPa | 0.1 | 0.31 |
Property | Requirement | Sample no. | Result |
---|---|---|---|
Sto Gold Coat® | The WRB applied over OSB must show no cracking, delamination or flaking, or any deleterious effects following 250 hours exposure to Xenon arc | 1 | Pass |
2 | Pass | ||
3 | Pass | ||
4 | Pass | ||
5 | Pass | ||
6 | Pass |
Reinforcing mesh
Property | Unit | Requirement | Result | ||
---|---|---|---|---|---|
Ash content | % | Report value | 14.7 | ||
Mass per unit area | g/m2 | Report value | 14 | ||
Breaking strength resistance | Weft | Warp | |||
Initial tensile strength | N/mm | ≥ 35 | 37.2 | 40.3 | |
Loss of tensile strength after | 28-day, 3-ion soak | % | ≤ 60% for adhered EIFS, ≤ 50% for mechanically fastened EIFS | 17.7 | 7.3 |
Residual tensile strength after | 28-day, 3-ion soak | N/mm | ≥ 15 N/mm for adhered EIFS, ≥ 25 N/mm for mechanically fastened EIFS | 30.6 | 37.3 |
Elongation at break | initial | % | Report value | 3.3 | 4.1 |
28-day, 3-ion soak | 2.8 | 3.8 |
Impact resistance
Property | Requirement | Result | |
---|---|---|---|
Sto BTS® Plus | 10 joules | 6/10 free-fall drops must show no perforation (broken mesh) | Pass |
3 joules | 6/10 free-fall drops must show no cracks | Pass | |
Sto Primer/Adhesive-B | 10 joules | 6/10 free-fall drops must show no perforation (broken mesh) | Pass |
3 joules | 6/10 free-fall drops must show no cracks | Pass |
Wind load resistance
Reference wind pressure (kPa) | Sustained | Cycling | Gust | Deflection test | |||||
---|---|---|---|---|---|---|---|---|---|
P1, P1′ (Pa) | P2, P2′ (Pa) | P3, P3′ (Pa) | Test pressure (Pa) 3.3 P1, P1′ | Measured maximum net mid-span deflections (mm) | |||||
Stud span 3 050mm | Sheathing span 406 mm | ||||||||
Q50 ≤ 0.45 | ±450 | Pass | ±660 | Pass | ±980 | Pass | +980 | 5.49 | 1.76 |
−980 | −5.59 | −2.35 | |||||||
Q50 ≤ 0.55 | ±550 | Pass | ±800 | Pass | ±1 200 | Pass | +1 200 | 6.72 | 2.16 |
−1 200 | −6.84 | −2.88 | |||||||
Q50 ≤ 0.65 | ±650 | Pass | ±950 | Pass | ±1 410 | Pass | +1 410 | 7.90 | 2.54 |
−1 410 | −8.04 | −3.38 | |||||||
Q50 ≤ 0.75 | ±750 | Pass | ±1 090 | Pass | ±1 630 | Pass | +1 630 | 9.13 | 2.93 |
−1 630 | −9.29 | −3.91 | |||||||
Q50 ≤ 0.85 | ±850 | Pass | ±1 240 | Pass | ±1 850 | Pass | +1 850 | 10.36 | 3.33 |
−1 850 | −10.55 | −4.44 | |||||||
Q50 ≤ 1.00 | ±1 000 | Pass | ±1 460 | Pass | ±2 180 | Pass | +2 180 | 12.21 | 3.92 |
−2 180 | −12.43 | −5.23 | |||||||
Maximum test pressure @ L/180 deflection | +3 073 | 16.90 | - | ||||||
−2 990 | −16.90 | - | |||||||
Ultimate structural test pressure | +3 640 | Passed | |||||||
−3 390 | Sheathing separation from steel studs occurred |
Joint disruption and relaxation resistance
Property | Unit | Requirement | Result | |
---|---|---|---|---|
Joint width | ||||
2 mm | 4 mm | |||
Joint disruption resistance | - | The WRB at joints on two assemblies must show no cracking, delaminating or any other deleterious effects at a transverse bending of L/180 Table footnote (1) | Pass | |
Joint extension @ L/180 | mm | Report value | 0.72 | 0.71 |
Property | Unit | Requirement | Sample no. | Result |
---|---|---|---|---|
Joint relaxation resistance | kg/m2·s | Five WRB-coated OSB specimens subjected to 1.3-mm extension following exposure to 15 24-h environmental cycles must have a maximum average water transmission rate of 2 × 10−7 kg/m2·s | 1 | 3.12 × 10−7 |
2 | 1.76 × 10−7 | |||
3 | 1.87 × 10−7 | |||
4 | 1.30 × 10−7 | |||
5 | 1.87 × 10−7 | |||
Average | 1.96 × 10−7 |
Drainage capacity
Property | Requirement | Result | ||
---|---|---|---|---|
Retained water per unit area (g/m2) | Drainage capacity (%) after 1 h | |||
After 1 h | After 48 h | |||
Panel 1Table footnote (1) | The water retained in the unit following 48 hours of drying must not be greater than 15 g/m2 for any single test specimen | 38.2 | 0.00 | 99.5 |
29.4 | 0.00 | |||
Panel 2Table footnote (1) | The water retained in the unit following 48 hours of drying must not be greater than 15 g/m2 for any single test specimen | 35.4 | 0.00 | 99.6 |
27.2 | 0.00 | |||
Panel 3Table footnote (1) | The drainage capacity must not be less than 98% of the water mass delivered into the EIFS wall specimen | 31.8 | 0.00 | 99.6 |
24.5 | 0.00 |
Nail popping resistance
Property | Requirement | Sample no. | Result |
---|---|---|---|
Nail popping resistance | There must be no cracking or delamination of the WRB following 1-mm nail protrusion from the nail’s original preset of 1 mm below the surface of the OSB substrate | 1 | Pass |
2 | Pass | ||
3 | Pass | ||
4 | Pass | ||
5 | Pass | ||
6 | Pass |
Fire testing
For a detailed description of the compliance of the related systems to the requirements of Article 3.1.5.5. of Division B of the NBC 2015, please refer to Intertek Listing Information of StoTherm®ci Lotusan, StoTherm®ci Classic, and StoTherm®ci Essence and SPEC ID:18188 Design No. STO/WEIFS 25-01. Refer to Design No. STO/WEIFS 15-01 for compliance to the requirements of Clause 3.2.3.8.(1)(b) of Division B of the NBC 2015.
Administrative information
Use of Canadian Construction Materials Centre (CCMC) assessments
This assessment must be read in the context of the entire CCMC Registry of Product Assessments, any applicable building code or by-law requirements, and/or any other regulatory requirements (for example, the Canada Consumer Product Safety Act, the Canadian Environmental Protection Act, etc.).
It is the responsibility of the user to confirm that the assessment they are using is current and has not been withdrawn or superseded by a later version on the CCMC Registry of Product Assessments.
Disclaimer
The National Research Council of Canada (NRC) has evaluated only the characteristics of the specific product described herein. The information and opinions in this evaluation are directed to those who have the appropriate degree of experience to use and apply its contents (such as authorities having jurisdiction, design professionals and specifiers). This evaluation is valid when the product is used as part of permitted construction, respecting all conditions and limitations stated in the evaluation, and in accordance with applicable building codes and by-laws.
This evaluation is provided without representation, warranty or guarantee of any kind, expressed or implied, and the NRC provides no endorsement for any evaluated product. The NRC accepts no responsibility whatsoever arising in any way from any and all use of or reliance on the information contained herein or the use of any evaluated product. The NRC is not undertaking to render professional or other services on behalf of any person or entity nor to perform any duty owed by any person or entity to another person or entity.
Language
Une version française de ce document est disponible.
In the case of any discrepancy between the English and French version of this document, the English version shall prevail.
Copyright
© His Majesty the King in Right of Canada, as represented by the National Research Council of Canada, 2023
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, without the prior written permission of the CCMC.
Page details
From: National Research Council Canada
- Date modified: